-33%
, ,

DKM405 Network Analyzer With Total Harmonic Distortion Display

DATAKOM

Key Features

  • True RMS measurements
  • Total harmonic distortion display
  • Max demand display
  • Configurable relay output
  • Energy pulse output capability
  • Optically isolated, configurable digital input
  • Active-reactive power counters
  • Hour counter
  • Voltage transformer ratio for MV applications
  • Front panel programming
  • Reduced panel depth
  • Wide operating temperature range
  • Sealed front panel (IP54)
  • Plug-in connection system
  • Click Here To Download DKM405 User Manual

 20,000.00  30,000.00

Compare

Buy all Datakom products like generator controllers, energy meters, panel meters, synchronization controllers, auto mains failures (AMF), auto transfer switches (ATS), generator battery chargers, etc, online in Pakistan. You can buy DKM405 Network Analyser with total harmonic distortion displayunit online or by visiting Electronic Power House (EPH) and Tetralink Technologies (TLT) in Lahore who are the authorized distributor of Datakom in Pakistan. All original Datakom products are available at very reasonable and best prices in Pakistan.

Features

  • True RMS measurements
  • Total harmonic distortion display
  • Max demand display
  • Configurable relay output
  • Energy pulse output capability
  • Optically isolated, configurable digital input
  • Active-reactive power counters
  • Hour counter
  • Voltage transformer ratio for MV applications
  • Front panel programming
  • Reduced panel depth
  • Wide operating temperature range
  • Sealed front panel (IP54)
  • Plug-in connection system

Description

The DKM-405 is a low-cost precision instrument designed to display various AC parameters in a 3-phase distribution panel. The standard unit is designed for a 230/400V network. A different version is available for 120/208V systems. The harmonic analysis is available for up to 31 harmonics. THD values of both voltage and current inputs are available. The optional digital input accepts both AC and DC signals and has programmable functions. The optional relay output is programmable. The relayfunction is selected through a list. The unit fits into a standard 92x92mm panel
opening.

Click Here To Download DKM405 User Manual

Technical Specifications

brands

DATAKOM

color

Black

Technical Specifications

Power Supply Input: 170 – 275VAC, 50 – 60Hz nominal (? 10%) Different AC supply voltages available.

Measurement Input Range: Voltage inputs: 10 – 300 V AC (L-N) 20 – 520 V AC (L-L)

Current inputs: 0.2 ? 5.5 A AC

Frequency: 30 – 100 Hz

Accuracy:Voltage: 0.5%+1digit Current: 0.5%+1 digit

Frequency: 0.5%+1 digit Power(kW,kVAr): 1.0%+2digit

Power factor: 2.0%+2digit

Measurement Range: CT range: 5/5A to 5000/5A VT range: 0.1/1 to 200.0/1 kW range: 0.1 kW to 6.5 MW

Power Consumption: < 4 VA Voltage burden: < 0.1VA per phase

Current burden: < 1VA per phase

Relay Outputs: 5A @ 250VAC

Digital Inputs: Active level: 5 to 30V-DC or AC

Min pulse duration: 250ms.

Isolation: 1000V AC, 1 minute

Operating Temperature: -20?C to +80?C (-4 to +176 ?F).

Maximum humidity: 95% non-condensing.

Degree of Protection: IP 54 (Front Panel) , IP 30 (Back panel)

Enclosure: Non-flammable, ROHS compliant, ABS/PC (UL94-V0)

Installation: Flush mounting with rear retaining brackets

Dimensions: 102x102x53mm (WxHxD)

Panel Cutout: 92x92mm Weight: 200 gr
EU Directives Conformity: 2006/95/EC (low voltage) 2004/108/EC (EMC)
Norms of reference: EN 61010 (safety requirements) EN 61326 (EMC requirements)
PACKAGING INFORMATION Pieces per Package: 12 pieces Package Size: 280 x 170 x 215mm (LxWxH) Package Weight: 2.6 kg

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “DKM405 Network Analyzer With Total Harmonic Distortion Display”

There are no reviews yet.