  • AS440 is a half-wave phase-controlled thyristor type AVR
  • Soft Shell with Stamoford Logo
  • Sensing Input: Voltage Jumper selectable 100-130 Vac 1 phase or 190-264 Vac 1 phase
  • Output:Voltage 82 V d. C. @ 200 V a. C
  • Frequency: 50-60 Hz nominal
  • Regulation:+/- 1.0%
  • Soft Shell
  • Stamford Logo on the back
  • Click Here To Download AS440 User Manual

 18,500.00  20,000.00

Compare

AVR AS440 for Stamford Generator with Soft Shell

Buy all Stamford AVRs and Rotating Rectifier assemblies in Pakistan. You can buy AVR AS440 for Stamford Generator with Soft Shell & Stamford Logo online anywhere from Pakistan or by visiting Electronic Power House(EPH) andTetralink Technologies(TLT) in Lahore who are the main distributors of Stamford in Pakistan. All original Stamford products are available at very reasonable and best prices in Pakistan

Key Features:

  • AS440 is a half wave phase-controlled thyristor type AVR
  • Soft Shell with Stmford Logo
  • Sensing Input:Voltage Jumper selectable 100-130 Vac 1 phase or 190-264 Vac 1 phase
  • Output:Voltage 82 V d. C. @ 200 V a. C
  • Frequency: 50-60 Hz nominal
  • Regulation:+/- 1.0%
  • Soft Shell
  • Stamford Logo on the back

General description

AS440 for Stamford generator is a half-wave phase-controlled thyristor type AVR and forms part of the excitation system for a brushless generator. The design employs Surface Mount Technology (SMT) for the high integration of features in a small footprint AVR.
Positive voltage builds up from residual levels is ensured by the use of efficient semiconductors in the power circuitry of the AVR. The power and voltage sensing circuits have separate terminals, allowing the excitation power to be derived directly from the stator winding for basic applications or from an auxiliary winding if sustained short circuit performance is required.
The AVR is linked with the main stator windings and the exciter field windings to provide closed-loop control of the output voltage with load regulation of +/- 1.0%.
The AVR voltage sensing terminals continuously sample the output windings for voltage control purposes. In response to this sample voltage, the AVR controls the power fed to the exciter field, and hence the main field, to maintain the machine output voltage within the specified limits, compensating for load, speed, temperature, and power factor, of the generator.
A frequency measuring circuit continually monitors the generator output and provides under-speed protection of the excitation system, by reducing the output voltage proportionally with speed below a pre-settable threshold. A manual adjustment is provided for the factory setting of the under frequency roll-off point, (UFRO). This can easily be changed to 50 or 60 Hz in the field by push-on link selection.
Over excitation conditions are limited to a safe period by a protection circuit within the AVR. Provision is made for the connection of a remote voltage
trimmer, allowing the user fine control of the generator’s output.
Analogue input is provided allowing connection to the Power Factor controller or other external devices with compatible output. The AVR has the facility for droop CT connection, to allow parallel running with other similarly equipped generators.

color

Black

Technical Specification

SENSING and POWER INPUT

Voltage? ?100-264 V ac 1 phase Frequency? ? ?50-60 Hz nominal

OUTPUT

Voltage? ? ? 82 V d.c. @ 200 Va.c power input. Voltage? ? ? 45 V d.c. @ 110 Va.c power input.

Current? ? continuous 5A (see note 1). transient 7.5A for 10 secs.

Resistance? ?15 ohms min

REGULATION

+/- 1.0% (see note 2)

THERMAL DRIFT

0.03% per deg. C change in AVR ambient (see note 3)

TYPICAL SYSTEM RESPONSE

AVR response?????????????????????????????????? 20ms

Field current to 90%???????????????????????? 80 ms

Machine Volts to 97%?????????????????????? 300ms

EXTERNAL VOLTAGE ADJUSTMENT

+/-10% with 1 k ohm 1 watt trimmer (see note 4) Increasing resistance lowers voltage.

Fixed 15kOhm resistor enables 110V sensing

UNDER FREQUENCY PROTECTION

Set point??????????????? 94 -98% Hz (see note 5)

UNIT POWER DISSIPATION

12 watts maximum

BUILD UP VOLTAGE

4 Volts @ AVR terminals

QUADRATURE DROOP INPUT

10 ohms burden

Max. sensitivity: 0.07 A for 5% droop 0PF Max. input: 0.33 A

OVER EXCITATION PROTECTION

Set point?????????? 67 Vdc +/-3% (fixed) Time delay?????????? 10-15 seconds (fixed)

ENVIRONMENTAL

Vibration?????????? 20-100 Hz??????????? 50mm/sec

100Hz ? 2kHz????? 3.3g

Operating temperature???????????????? -40 to +70C (note 6)

Relative Humidity 0-70C????????????? 95% (note 7)

Storage temperature??????????????????? -55 to +80C

 